Plan the power and cooling before the cluster arrives.

Most server rooms weren’t built for the power and cooling a GPU cluster needs. We help you plan for these requirements, so your cluster runs the day it arrives.

How power and cooling reach a cluster rackSide view of a server room. A power panel feeds the rack through A and B circuits under the floor. A cooling unit pushes cold air under the raised floor and up through a perforated tile into the front of the rack. Hot air leaves the back of the GPU servers into the hot aisle, rises to the ceiling and returns to the cooling unit.

Why it matters

GPU clusters have outgrown most server rooms.

In 2026, the typical data center rack runs at about 7.8 kW, up just 0.3 kW from a year earlier. For example, a cluster of four 8-GPU servers draws about 57 kW, more than seven typical racks’ worth, before you add the network switches, storage and head node. Rack space is rarely the problem. Power, cooling, weight and depth usually are.

The good news: every one of these is solvable when it’s planned early. We review your space, specify what you need, and work with your facilities team and electrician, so there are no surprises on install day.

The limits, and how we plan for them

What a GPU cluster asks of your room.

Circuits
Redundancy
Heat
Rack space
How we help

Size the circuits to the cluster

Each 8-GPU server draws about 14.3 kW, and a 208 V, 30 A circuit gives you about 5 kW you can use. For four servers, that means four 208 V, 60 A three-phase circuits per side, plus power for the network, storage and head node. We specify every circuit in writing your electrician can work from.

Make redundancy actually redundant

With A and B feeds, each side has to carry the whole cluster on its own. We size every feed for the full load, so a failure on one side doesn’t take your cluster down.

Plan the cooling, not just the power

Nearly every watt becomes heat: about 16 tons of cooling for four 8-GPU servers, before the rest of the cluster. We work out the load with your facilities team and recommend the airflow, containment or liquid cooling to match.

Plan by capacity, not rack units

Four 10U servers fit in one 42U rack, but together they draw about 57 kW, more than seven times what a typical rack is built for. We lay out the cluster across racks around power, cooling, weight and depth.

Planned before the servers arrive

From site review to power-up, we work through every limit with you before you order, and we rack, cable and power up the cluster on site.

How many circuits does a GPU cluster need?A cluster is built up one 8-GPU server at a time. Each server draws about 14.3 kW and gets its own 208 volt 60 amp three-phase circuit on Feed A and on Feed B, each with about 17.3 kW usable. Four servers draw about 57 kW and need four circuits per side, plus power for the network, storage and head node.HOW MANY CIRCUITS DOES THE CLUSTER NEED?THE CLUSTERTHE PANELFeed AFeed B8-GPU server 114.3 kW60 A · 3-phase14.3 of 17.3 kW60 A · 3-phase14.3 of 17.3 kW8-GPU server 214.3 kW60 A · 3-phase14.3 of 17.3 kW60 A · 3-phase14.3 of 17.3 kW8-GPU server 314.3 kW60 A · 3-phase14.3 of 17.3 kW60 A · 3-phase14.3 of 17.3 kW8-GPU server 414.3 kW60 A · 3-phase14.3 of 17.3 kW60 A · 3-phase14.3 of 17.3 kWNetwork, storage, head nodeSized to matchSized to matchGPU SERVER LOAD60 A CIRCUITS14.3 kW1per side, 2 in all28.6 kW2per side, 4 in all42.9 kW3per side, 6 in all~57 kW4per side, 8 in allEach 8-GPU server gets its own 208 V, 60 A three-phase circuit on each feedFour servers: about 57 kW, four circuits per side, plus the rest of the clusterUsable power is 80% of the breaker rating. Actual draw depends on the configuration.

Sources: server power from NVIDIA DGX B200; size and weight from the NVIDIA DGX B200 User Guide; typical rack density from the Uptime Institute 2026 Global Data Center Survey, with the 2025 comparison from Data Center Knowledge. Figures are for planning; we confirm them for your configuration.

Before you order

Questions for your facilities team.

The answers help us size everything correctly. Don’t have them all? That’s what a site review is for, and we’ll find them with you.

Power

What feeds each rack?

Voltage, amps, single- or three-phase, and how many circuits. Are there separate A and B feeds, and can the UPS and generator carry the new load?

Cooling

How much heat can the room remove?

Cooling capacity per rack and for the whole room, in kW or tons, and how much of it is already in use.

Airflow

Where does the hot air go?

Whether the room has hot and cold aisles, and whether they’re contained. Modern compute and GPU nodes move a lot of air, front to back.

Floor and racks

What can they hold?

Load ratings for the floor, especially a raised floor, and for the racks themselves. Four GPU servers can weigh over 1,200 lb.

Rack depth

Will the servers fit inside?

The usable depth with the doors closed. GPU servers run about 35 inches deep before power and network cables.

Getting it in

How will it reach the rack?

Doorways, elevators, the loading dock, and whether a server lift is available on site.

When the room isn’t ready

There’s almost always a way.

A room that can’t take a modern cluster today usually can with the right plan. These are the options we work through with you.

Spread the load

Fewer servers per rack, so each rack stays within the power and cooling it actually has.

Upgrade the circuits

208 V, 60 A three-phase feeds sized for each server, with separate A and B sides.

Add targeted or liquid cooling

Rear-door heat exchangers, in-row cooling, or direct liquid cooling for the densest racks. We’ll recommend what fits, and can help source it if you’d like.

Use a colocation facility

A high-density colocation facility can supply the power and cooling your room can’t. We’ll plan the install there just as we would in your own room.

Right-size the hardware

A 4-GPU or PCIe GPU configuration may deliver what you need on the power you have today.

Phase it in

Start with what your room supports now, and add nodes as power and cooling upgrades land.

Planning a GPU cluster? Start with your room.